Technical Data:
| 
 Performances 
 | 
| 
 Air temperature 
 | 
 [°C] 
 | 
 32 
 | 
| 
 Evaporator inlet water temperature 
 | 
 [°C] 
 | 
 26 
 | 
| 
 Evaporator outlet water temperature 
 | 
 [°C] 
 | 
 21 
 | 
| 
 Ethylene glycol 
 | 
 --- 
 | 
 0% 
 | 
| 
 Cooling capacity 
 | 
 [kW] 
 | 
 23,26 
 | 
| 
 Compressors power input 
 | 
 [kW] 
 | 
 6,06 
 | 
| 
 Total power input 
 | 
 [kW] 
 | 
 9,46 
 | 
| 
 Total absorbed current 
 | 
 [A] 
 | 
 16,75 
 | 
| 
 Energy efficiency (pumps excluded) 
 | 
 EER 
 | 
 3,41 
 | 
| 
 Water flow (laser source) 
 | 
 [l/h] 
 | 
 4000 
 | 
| 
 Available pressure (laser source) 1 
 | 
 [kPa] 
 | 
 298 
 | 
| 
 Water flow (optics) 
 | 
 [l/h] 
 | 
 600 
 | 
| 
 Available pressure (optics) 1 
 | 
 [kPa] 
 | 
 480 
 | 
| 
 Electrical Data 
 | 
| 
 Maximum power input (total) 
 | 
 [kW] 
 | 
 10,33 
 | 
| 
 Maximum absorbed current (total) 
 | 
 [A] 
 | 
 21,47 
 | 
| 
 Starting current 
 | 
 [A] 
 | 
 91,41 
 | 
| 
 Fan power 
 | 
 [kW] 
 | 
 0,77 
 | 
| 
 Fan current 
 | 
 [A] 
 | 
 1,70 
 | 
| 
 Fans quantity 
 | 
 [#] 
 | 
 1 
 | 
| 
 Pump power input (laser source) 
 | 
 [kW] 
 | 
 1,31 
 | 
| 
 Pump absorbed current (laser source) 
 | 
 [A] 
 | 
 2,41 
 | 
| 
 Pump power input (optics) 
 | 
 [kW] 
 | 
 1,33 
 | 
| 
 Pump absorbed current (optics) 
 | 
 [A] 
 | 
 2,30 
 | 
| 
 Power supply 
 | 
 [V/Ph/Hz] 
 | 
 400/3/50 
 | 
| 
 IP protection degree 
 | 
 --- 
 | 
 IP44 
 | 
| 
 Technical Data 
 | 
| 
 Refrigerant 
 | 
 --- 
 | 
 R513A 
 | 
| 
 Compressor quantity 
 | 
 [#] 
 | 
 1 
 | 
| 
 Refrigeration circuit quantity 
 | 
 [#] 
 | 
 1 
 | 
| 
 Air flow 
 | 
 [m3/h] 
 | 
 7 300 
 | 
| 
 Sound pressure level at 10 m in free field 
 | 
 [dbA] 
 | 
 50 
 | 
| 
 Water connections size: 
Source - Auxiliaries - Optics 
 | 
 [inch] 
 | 
 1"1/4 - 3/4"-1/2" 
 | 
| 
 Tank capacity 
 | 
 [dm3] 
 | 
 100 
 | 
| 
 Width 
 | 
 [mm] 
 | 
 760 
 | 
| 
 Depth 
 | 
 [mm] 
 | 
 780 
 | 
| 
 Height 
 | 
 [mm] 
 | 
 1.800 
 | 
| 
 Weight (approx.) 
 | 
 [kg] 
 | 
 315 
 | 
 
1 Max head pressure at 26/21@32°C adjustable with the water bypass installed for standard both on the source and on optics sides.