Refrigeration Air Dryers PCD Series

LOW OUTLET TEMPERATURE REFRIGERATION DRYERS

Flow rate: 12 ÷ 720 m3/h

PCD (Process Chiller-Dryer) refrigeration dryers, called “Point of Use Dryers”, are used in situations where a compressed air temperature...

PCD refrigeration dryers (Process Chiller-Dryer), called “Point of Use Dryer" are used in situations where a compressed air temperature equal to the Dew-Point value is required (Dew -Point such as the moulding sector of plastics and foodstuffs, and sectors where it is not possible to use water for cooling.

In addition to the electronic controller (Industry 4.0 ready), the range features a single air-to-cooler (or evaporator) heat exchange circuit. The incoming warm and humid air exchanges heat with the refrigerant fluid counter-current flow, undergoing an abrupt temperature drop. Before leaving the dryer, the cold air is conveyed into the stainless-steel demister separator where the condensate is collected and discharged from the system. The treated air exits at a temperature close to thedew point. 


MAXIMUM WORKING CONDITIONS

  • Ambient temperature: + 50°C
  • Inlet air pressure: 15 barg
  • Inlet air temperature: + 55°C

Model

Air flow

Power Supply

Connections

[m3/h]

[l/min]

[scfm]

[Ph/Volt/Fr]

[ Ø ]

PCD 2C

12

200

7

1/230/50-60

G 3/8” BSP-F

PCD 6C

36

600

21

1/230/50-60

G 3/8” BSP-F

PCD 10

60

1 000

35

1/230/50

G 3/4” BSP-F

PCD 15

90

1 500

53

1/230/50

G 3/4” BSP-F

PCD 20

116

1 930

68

1/230/50

G 3/4” BSP-F

PCD 25

150

2 500

88

1/230/50

G 1” BSP-F

PCD 40

240

4 000

141

1/230/50

G 1” BSP-F

PCD 60

360

6 000

212

1/230/50

G 1.1/2” BSP-F

PCD 80

480

8 000

283

3/400/50

G 2” BSP-F

PCD 100

600

10 000

353

3/400/50

G 2” BSP-F

PCD 120

720

12 000

424

3/400/50

G 2” BSP-F

Data refer to the following nominal condition: ambient temperature + 25 °C; inlet air pressure 7 barg; inlet air temperature +35 °C; outlet air temperature +5 °C.

  • Copper coaxial heat exchanger (PCD 2C÷6C)
  • Stainless steel plate heat exchanger (PCD 10÷250)
  • High-efficiency compressor
  • Generously sized condenser unit
  • Valvola pressostatica per acqua (raffredd. ad acqua) (PCD 25÷250)
  • Controller digitale DMC35 (PCD2÷6), DMC34 (PCD10÷60), DMC24 (PCD80÷120) RS485 modbus
  • Refrigerant compressor thermal or thermo-ammeter protection
  • Automatic condensation pressure control
  • High compressor temperature protection (PCD 25÷120)
  • Refrigerant compressor phase sequence relay protection (3ph models)
  • Refrigerant high-pressure and low-pressure safety pressure switches (PCD 60÷120)
  • Hot gas bypass valve
  • Timed condensation drain
  • Compressor crankcase heater (3ph models only)
PCD Thumbnail
DMC34-1.jpg

DMC34

Electronic controller
TAC.jpg

TAC

Anti corrosion treatment
BK.jpg

BK

Zero loss drain
WC 2 .jpg

WC

Water Cooling with plates condenser
WC_TBH-3.jpg

WC TBH

Water cooling. Tube bundle condenser
SERVICE-UNIT.jpg

SERVICE UNIT

8.000 hours maintenance kit for BK type electronic drain